Direct-to-chip cooling
Cold plates collect chip heat; manifolds and a CDU transfer it to the facility loop. Remaining air heat needs separate cooling.
ALICE™ PMDC · ENGINEERING
Direct-to-chip (D2C) is our baseline. Immersion is a project-specific alternative for compatible AI and HPC hardware.

Cold plates collect chip heat; manifolds and a CDU transfer it to the facility loop. Remaining air heat needs separate cooling.

ALICE™ PMDC — single-phase immersion cooling concept; illustrative, not an as-built installation.
Compatible servers sit in dielectric liquid. The fluid remains liquid and circulates through a heat exchanger.
Illustrative concept; not a certified product or completed installation.
The fluid boils at heated surfaces and condenses in a controlled system. Fluid availability, environmental obligations and vapor containment require review.
Confirm server warranty, fluid compatibility, viscosity, dielectric strength, seals, cables, thermal interfaces, filtration and fluid ageing. Assess fire risk, spill containment, tank mass, floor loading, lifting clearance and maintenance procedures.
Tank → dielectric loop → heat exchanger → facility water loop → dry cooler or other site-selected heat rejection. Pump redundancy and control logic are engineered per project.
Verify heat load, flow, temperatures, alarms, pump failover, leak response and recovery at agreed test conditions. No guaranteed PUE or capacity without supplier validation.