Cooling loop qualification
Confirm OEM coolant temperature, chemistry, flow and pressure limits; size the CDU at the actual approach temperature and verify residual air load.
ALICE™ PMDC · ENGINEERING
Design decisions backed by project evidence, not marketing ratings.
Confirm OEM coolant temperature, chemistry, flow and pressure limits; size the CDU at the actual approach temperature and verify residual air load.
Obtain written hardware and fluid compatibility, service and warranty approval; assess wet mass, spill containment, fluid ageing and fire risk.
Compare dry, adiabatic and mechanical cooling against design weather, water availability and required supply temperature; verify capacity at design conditions.
Require single-line diagrams, short-circuit and protection studies, equipment loads, transport and anchorage calculations, and verified service clearances.
Define FAT and SAT loads, measurement accuracy, alarm limits, failure scenarios and recovery criteria before testing. Record exceptions and close them before release.